9.17 Z: Bypass Parameters
668 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
No.
(Hex.)
Name Description
Default
(Range)
Ref.
Z2-08
(856A)
Digital Input 8 Function
(TB2-8)
Sets the function for bypass digital input 8. 0
(0 - 47)
442
Z2-09
(856B)
Digital Input 1 Invert
Select
Inverts the output of the function selected in Digital Input 1.
0 : Normal (Non-inverted)
1 : Inverted
0
(0, 1)
443
Z2-10
(856C)
Digital Input 2 Invert
Select
Inverts the output of the function selected in Digital Input 2.
0 : Normal (Non-inverted)
1 : Inverted
0
(0, 1)
443
Z2-11
(856D)
Digital Input 3 Invert
Select
Inverts the output of the function selected in Digital Input 3.
0 : Normal (Non-inverted)
1 : Inverted
0
(0, 1)
443
Z2-12
(856E)
Digital Input 4 Invert
Select
Inverts the output of the function selected in Digital Input 4.
0 : Normal (Non-inverted)
1 : Inverted
0
(0, 1)
443
Z2-13
(856F)
Digital Input 5 Invert
Select
Inverts the output of the function selected in Digital Input 5.
0 : Normal (Non-inverted)
1 : Inverted
0
(0, 1)
443
Z2-14
(8570)
Digital Input 6 Invert
Select
Inverts the output of the function selected in Digital Input 6.
0 : Normal (Non-inverted)
1 : Inverted
0
(0, 1)
443
Z2-15
(8571)
Digital Input 7 Invert
Select
Inverts the output of the function selected in Digital Input 7.
0 : Normal (Non-inverted)
1 : Inverted
0
(0, 1)
444
Z2-16
(8572)
Digital Input 8 Invert
Select
Inverts the output of the function selected in Digital Input 8.
0 : Normal (Non-inverted)
1 : Inverted
0
(0, 1)
444
Z2-23
(8579)
Digital Output 7 (TB1
1~3)
Sets the function for bypass digital output 7. 7
(0 - 99)
448
Z2-24
(857A)
Digital Output 8 (TB1
4~6)
Sets the function for bypass digital output 8. 10
(0 - 99)
448
Z2-25
(857B)
Digital Output 9 (TB1
7~9)
Sets the function for bypass digital output 9. 12
(0 - 99)
448
Z2-26
(857C)
Digital Output 10 (TB1
10~12)
Sets the function for bypass digital output 10. 15
(0 - 99)
448
Z2-30
(8580)
Analog Input Signal
Level Select
Sets the input signal level for MFAI terminal A1.
0 : 0 to 10V (Lower Limit at 0)
2 : 4 to 20 mA
3 : 0 to 20 mA
0
(0 - 3)
452
Z2-32
(8582)
Analog Input Gain
Setting
Sets the gain of the analog signal input to MFAI terminal A1. 100.0%
(-999.9 - +999.9%)
452
Z2-33
(8583)
Analog Input Bias Setting Sets the bias of the analog signal input to MFAI terminal A1. 0.0%
(-999.9 - +999.9%)
452
Z2-xx: Digital Input Setting Values
Setting Value Function Description Ref.
0 Not Used Use this setting for unused terminals or to use terminals in through mode. 444
1 Drive S1 Passthrough Drive Multi-function input S1. 444
2 Drive S2 Passthrough Drive Multi-function input S2. 444
3 Drive S3 Passthrough Drive Multi-function input S3. 444
4 Drive S4 Passthrough Drive Multi-function input S4. 444
5 Drive S5 Passthrough Drive Multi-function input S5. 444
6 Drive S6 Passthrough Drive Multi-function input S6. 444
7 Drive S7 Passthrough Drive Multi-function input S7. 445

Table of Contents