Parameter List
9
9.18 U: Monitors
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference 681
No.
(Hex.)
Name Description MFAO Signal Level
U5-03
(0064)
PID Output Shows the PID control output as a percentage of the maximum output frequency.
Unit: 0.01%
10 V: Maximum frequency
(0 V to +10 V)
U5-04
(0065)
PID Setpoint Shows the PID setpoint.
Unit: 0.01%
Note:
Parameters b5-46 [PID Unit Display Selection], b5-38 [PID User Unit Display Scaling], and b5-
39 [PID User Unit Display Digits] set the unit, range, and resolution.
10 V = Maximum frequency
(-10 V to +10 V)
U5-05
(07D2)
PID DifferentialFdbk Shows the PID differential feedback value as a percentage of the maximum output frequency.
This monitor is available after you set H3-02 or H3-10 = 16 [Terminal A1/A2 Function Selection =
Differential PID Feedback].
Unit: 0.01%
10 V = Maximum frequency
(-10 V to +10 V)
U5-06
(07D3)
PID FdbkDif PID Fdbk Shows the difference from calculating U5-05 [PID DifferentialFdbk] - U5-01[PID Feedback].
Unit: 0.01%
Note:
U5-01 [PID Feedback] = U5-06 when H3-02 or H3-10 16 [Terminal A1/A2 Function Selection
Differential PID Feedback].
10 V = Maximum frequency
(-10 V to +10 V)
U5-07
(0072)
AUTO Mode Freq Ref Shows the Frequency reference value at AUTO Mode.
Unit: 0.01 Hz
Note:
Parameter o1-03 [Frequency Display Unit Selection] sets the display unit.
No signal output available
U5-08
(0073)
HAND Mode Freq Ref Shows the Frequency reference value at HAND Mode.
Unit: 0.01 Hz
Note:
Parameter o1-03 [Frequency Display Unit Selection] sets the display unit.
No signal output available
U5-14
(086B)
PID Out2 Upr4 Digits Shows the custom PI output.
Monitor U5-14 shows the upper four digits and U5-15 [PID Out2 Lwr4 Digits] shows the lower four
digits.
The drive uses b5-43 [PID Out2 Monitor MAX Upper4 Dig] and b5-44 [PID Out2 Monitor MAX
Lower4 Dig] to scale the monitors.
Unit: 1
Note:
Parameter b5-41 [PID Output 2 Unit] sets the display unit.
10 V = b5-43 × 10000
U5-15
(086C)
PID Out2 Lwr4 Digits Shows the custom PI output.
Monitor U5-14 shows the upper four digits and U5-15 [PID Out2 Lwr4 Digits] shows the lower four
digits.
The drive uses b5-43 [PID Out2 Monitor MAX Upper4 Dig] and b5-44 [PID Out2 Monitor MAX
Lower4 Dig] to scale the monitors.
Unit: 0.01
Note:
Parameter b5-41 [PID Output 2 Unit] sets the display unit.
b5-43 > 0: 10 V = 10000
b5-43 = 0: 10 V = b5-44
U5-16
(086D)
PI Aux Ctrl Feedback Shows the PI Auxiliary Control Feedback level from the terminal set for H3-xx = 27 [PI Auxiliary
Control Feedback].
Unit: PSI
Note:
Parameters YF-21 [PI Aux Ctrl Level Unit Selection] and YF-22 [PI Aux Level Decimal Place
Pos] set the unit and resolution.
No signal output available
U5-17
(086E)
PI2 Control Setpoint Shows the PI2 Control setpoint.
Note:
Parameters S3-04 [PI2 Control Unit Selection] and S3-03 [PI2 Control Decimal Place Pos] set
the unit and resolution.
10 V = S3-02
U5-18
(086F)
PI2 Control Feedback Shows the PI2 Control Feedback Level from the terminal set for H3-xx = 26 [PI2 Control
Feedback].
Note:
Parameters S3-04 [PI2 Control Unit Selection] and S3-03 [PI2 Control Decimal Place Pos] set
the unit and resolution.
10 V = S3-02
U5-19
(0870)
PI2 Control Input Shows the PI2 Control input (deviation between PI target and feedback).
Note:
Parameters S3-04 [PI2 Control Unit Selection] and S3-03 [PI2 Control Decimal Place Pos] set
the unit and resolution.
10 V = S3-02
U5-20
(0871)
PI2 Control Output Shows the PI2 Control output.
Note:
Parameters S3-04 [PI2 Control Unit Selection] and S3-03 [PI2 Control Decimal Place Pos] set
the unit and resolution.
The drive operation while H1-xx = A8 or 1A8 [PI2 Control Disable] changes when the S3-12
[PI2 Control Disable Mode Sel] setting changes.
10 V = S3-02