9.19 Defaults by Bypass and Drive Model
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference 693
No. Name Unit Default
-
Bypass
Model
- B052 B065 B077 B096 B124 B156 B180 B240 B302
o2-04
Drive
Model
(KVA)
Selection
Hex. A0 A2 A3 A4 A5 A6 A7 A8 A9
E2-11
Motor
Rated
Power
HP
(kW)
30
(22)
40
(30)
50
(37)
60
(45)
75
(55)
100
(75)
125
(90)
150
(110)
200
(160)
L2-02
Power Loss
Ride
Through
Time
s 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
L2-03
Minimum
Baseblock
Time
s 1.0 1.1 1.1 1.2 1.2 1.3 1.5 1.7 1.8
L2-04
Powerloss V/
f Recovery
Ramp Time
s 0.6 0.6 0.6 0.6 1.0 1.0 1.0 1.0 1.0
L2-05
Undervoltage
Detection Lvl
(Uv1)
- 380 380 380 380 380 380 380 380 380
L3-24
Motor Accel
Time for
Inertia Cal
s 0.355 0.323 0.320 0.387 0.317 0.533 0.592 0.646 0.777
L8-02
Overheat
Alarm Level
°C 123 123 120 124 124 110 120 120 125
L8-09
Output
Ground Fault
Detection
- 1 1 1 1 1 1 1 1 1
L8-35
Installation
Method
Selection
- 2 2 2 2 2 2 0 0 0
L8-38
Carrier
Frequency
Reduction
- 2 2 2 2 2 2 2 2 2
n1-01
Hunting
Prevention
Selection
- 1 1 1 1 1 1 1 1 1
n1-03
Hunting
Prevention
Time
Constant
ms 10 10 10 10 30 30 30 30 30