10.3 BACnet Communications
710 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Object ID
Object Name
(Network Display, if
Different)
Modbus Reg. Active Text Inactive Text PV Access
BV61
Bypass Transfer to Bypass
Cmd
(BYP Xfer to BYP CMD)
8400h: Bit 3 ON OFF C
BV62
Emergency Override Bypass
(Em Over BYPASS CMD)
8400h: Bit 4 ON OFF C
BV63
Emergency Override Drive
Forward
(Em Over DRV FWD CMD)
8400h: Bit 5 ON OFF C
BV64
Bypass Motor OR Select
Command
(BYP Mtr OR Sel CMD)
8400h: Bit 6 ON OFF C
BV65
Bypass Motor AND Select
Command
(BYP Mtr AND Sel CMD)
8400h: Bit 7 ON OFF C
BV66 Not Used BV066 - ON OFF R
BV67 Not Used BV067 - ON OFF R
BV68 Not Used BV068 - ON OFF R
BV69
Bypass BYPASS Select
Command
(BYP BYPASS Sel CMD)
8400h: Bit C ON OFF C
BV70
Bypass Fault Reset
Command
(BYP Fault Reset CMD)
8400h: Bit D ON OFF C
BV71
Bypass External Fault
Command
(BYP Ext Fault CMD)
8400h: Bit E ON OFF C
BV72
Bypass DI-01 Command
(BYP DI-01 Command)
8402h: Bit 0 ON OFF C
BV73
Bypass DI-02 Command
(BYP DI-02 Command)
8402h: Bit 1 ON OFF C
BV74
Bypass DI-03 Command
(BYP DI-03 Command)
8402h: Bit 2 ON OFF C
BV75
Bypass DI-04 Command
(BYP DI-04 Command)
8402h: Bit 3 ON OFF C
BV76
Bypass DI-05 Command
(BYP DI-05 Command)
8402h: Bit 4 ON OFF C
BV77
Bypass DI-06 Command
(BYP DI-06 Command)
8402h: Bit 5 ON OFF C
BV78
Bypass DI-07 Command
(BYP DI-07 Command)
8402h: Bit 6 ON OFF C
BV79
Bypass DI-08 Command
(BYP DI-08 Command)
8402h: Bit 7 ON OFF C
BV80
Bypass HAND Mode Status
(BYP HAND Mode Status)
8784h: Bit 0 ON OFF R
BV81
Bypass OFF Mode Status
(BYP OFF Mode Status)
8784h: Bit 1 ON OFF R
BV82
Bypass AUTO Mode Status
(BYP AUTO Mode Status)
8784h: Bit 2 ON OFF R
BV83
Bypass DRIVE Mode Status
(BYP DRV Mode Status)
8784h: Bit 3 ON OFF R
BV84
Bypass BYPASS Mode
Status
(BYP BYPASS Mode Stat)
8784h: Bit 4 ON OFF R
BV85
Bypass Emergency Run
Bypass Status
(BYP Smk Prg BYP Stat)
8784h: Bit 5 ON OFF R