EasyManuals Logo

YASKAWA HV600 User Manual

YASKAWA HV600
794 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #711 background imageLoading...
Page #711 background image
Network Communications
10
10.3 BACnet Communications
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference 711
Object ID
Object Name
(Network Display, if
Different)
Modbus Reg. Active Text Inactive Text PV Access
BV86
Bypass Emergency Run
Drive Fwd Status
(BYP Smk Prg DRV Stat)
8784h: Bit 6 ON OFF R
BV87
Bypass Safety Status
(BYP Safety Status)
8784h: Bit 7 ON OFF R
BV88
Bypass BAS Interlock Status
(BYP BAS Interlk Stat)
8785h: Bit 0 ON OFF R
BV89
Bypass Run Status
(BYP RUN Status)
8785h: Bit 1 ON OFF R
BV90
Bypass Fault Status
(BYP Fault Status)
8785h: Bit 2 ON OFF R
BV91
Bypass Auto Transfer Status
(BYP Auto Xfer Status)
8785h: Bit 3 ON OFF R
BV92
Bypass Remote Transfer
Status
(BYP Remote Xfer Stat)
8785h: Bit 4 ON OFF R
BV93
Bypass Energy Savings
Status
(BYP Energy Save Stat)
8785h: Bit 5 ON OFF R
BV94
Bypass Motor 1 Select
Status
(BYP Motor 1 Sel Stat)
8785h: Bit 6 ON OFF R
BV95
Bypass Motor 2 Select
Status
(BYP Motor 2 Sel Stat)
8785h: Bit 7 ON OFF R
BV96
Bypass Drive Fault Status
(BYP Drive Flt Status)
8786h: Bit 0 ON OFF R
BV97
Bypass Safety Fault Status
(BYP Safety Flt Stat)
8786h: Bit 1 ON OFF R
BV98
Bypass BAS Interlock Fault
Status
(BYP BAS ILock Status)
8786h: Bit 2 ON OFF R
BV99
Bypass External Fault Status
(BYP Ext Fault Stat
8786h: Bit 3 ON OFF R
BV100 Not Used BV100 - - - R
BV101
Bypass Motor OL Status
(BYP Motor OL Stat)
8786h: Bit 5 ON OFF R
BV102
Bypass Motor 1 OL Status
(BYP Motor 1 OL Stat)
8786h: Bit 6 ON OFF R
BV103
Bypass Motor 2 OL Status
(BYP Mtr 2 OL Stat)
8786h: Bit 7 ON OFF R
BV104
Bypass Input Phase Loss
Status
(BYP Input Phase Loss)
8787h: Bit 0 ON OFF R
BV105
Bypass Drive Comms Status
(BYP Drive Comms)
8787h: Bit 2 ON OFF R
BV106
Bypass Loss of Load Status
(BYP Loss Of Load)
8787h: Bit 5 ON OFF R
BV107
Option Board on Drive
Status
(BYP Option Brd Comms)
8787h: Bit 4 ON OFF R
â–  Device Object
The Device Object is the BACnet device to the network in this manual. The Device Object Instance ID, the Device
Object Name, and the Device Object Location are configurable. Refer to Table 10.5 for more information.

Table of Contents

Other manuals for YASKAWA HV600

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA HV600 and is the answer not in the manual?

YASKAWA HV600 Specifications

General IconGeneral
CategoryDC Drives
SeriesHV600
Overload Capacity150% for 60 seconds
Output Voltage0 - Input Voltage
EnclosureNEMA 1, NEMA 12
CommunicationEthernet/IP, Modbus, DeviceNet, Profibus
SafetySafe Torque Off (STO)
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Short Circuit
Humidity5-95% (non-condensing)
AltitudeUp to 1000m (3280ft) without derating
Control MethodVector Control