10.6 MEMOBUS/Modbus Communications
754 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Register No.
(Hex.)
Description
8403
Bypass MFDO command
Controls the bypass digital outputs when the function is programmed to Unused.
bits 0 to 5 Reserved
bit 6 Multi-Function Digital Output 7 (TB1 1-3)
bit 7 Multi-Function Digital Output 8 (TB1 4-6)
bit 8 Multi-Function Digital Output 9 (TB1 7-9)
bit 9 Multi-Function Digital Output 10 (TB1 10-12)
All other bits Reserved
■ Monitor Data
You can only read monitor data.