EasyManua.ls Logo

YASKAWA HV600

YASKAWA HV600
794 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Network Communications
10
10.6 MEMOBUS/Modbus Communications
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference 755
Table 10.31 Monitor Data for MEMOBUS/Modbus Communication
Register No.
(Hex.)
Description
0020
Drive Status 1
bit 0
During drive run or bypass run
Set during drive run or bypass run.
1: During run, 0: During stop
bit 1
During reverse
1: During reverse, 0: Forward run
bit 2
System ready
1: Ready, 0: Not ready
bit 3
Drive faulted or bypass faulted
1: Fault
bit 4
oPE fault on drive or bypass
1: oPExx error
bit 5
MFDO (terminal M1-M2)
1: ON, 0: OFF
bit 6
MFDO (terminal M3-M4)
1: ON, 0: OFF
bit 7
MFDO (terminal M5-M6)
1: ON, 0: OFF
bit 8 - D Reserved
bit E
Bypass ComRef status
1: Enabled
bit F
Bypass ComCtrl status
1: Enabled
0021
Fault Description 1
bit 0 oC [Overcurrent], GF [Ground Fault]
bit 1 ov [Overvoltage]
bit 2 oL2 [Drive Overloaded]
bit 3 oH1 [Heatsink Overheat], oH2 [External Overheat (H1-XX=B)]
bit 4 - 6 Reserved
bit 7 EF0 [Option Card External Fault], EF1 to EF7 [External Fault]
bit 8
CPFxx [Hardware Fault]
Note:
Includes oFx.
bit 9
oL1 [Motor Overload], oL3, oL4 [Overtorque Detection 1/2], UL3, UL4 [Undertorque Detection 1/2]
bit A oS [Overspeed], dEv [Speed Deviation]
bit B During Uv [Undervoltage] detection
bit C Uv1 [DC Bus Undervoltage], Uv2 [Control Power Undervoltage], Uv3 [Soft Charge Answerback Fault]
bit D LF [Output Phase Loss], PF [Input Phase Loss]
bit E CE [Modbus Communication Error], bUS [Option Communication Error]
bit F oPr [Keypad Connection Fault]
0022
Fault Contents
bit 0 1: During data writing, during motor switching
bit 1 - 2 Reserved
bit 3 1: Upper/Lower Limit Fault
bit 4 1: Data Integrity Fault
bit 5 1: During EEPROM writing
bit 6 - F Reserved

Table of Contents

Other manuals for YASKAWA HV600

Related product manuals