EasyManua.ls Logo

YASKAWA HV600

YASKAWA HV600
794 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10.6 MEMOBUS/Modbus Communications
756 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Register No.
(Hex.)
Description
0023
U1-01 [Frequency Reference]
Note:
o1-03 [Frequency Display Unit Selection] sets the units.
0024
U1-02 [Output Frequency]
Note:
o1-03 [Frequency Display Unit Selection] sets the units.
0025
U1-06 [Output Voltage Ref] (units: 0.1 V)
Note:
Use H5-10 [Modbus Register 0025H Unit Sel] to change the setting unit.
0026
Ub-01 [Output Current] (units: 0.1 A)
0027 U1-08 [Output Power]
0028 U1-09 [Torque Reference]
0029
Fault Description 2
bit 0 Reserved
bit 1 GF [Ground Fault]
bit 2 PF [Input Phase Loss]
bit 3 LF [Output Phase Loss]
bit 4 - 5 Reserved
bit 6 oH4 [Motor Overheat Fault (PTC Input)]
bit 7 - F Reserved
002A
Minor Fault Description 1
bit 0 - 1 Reserved
bit 2 EF [FWD/REV Run Command Input Error]
bit 3 bb [Baseblock]
bit 4 oL3 [Overtorque 1]
bit 5 oH [Heatsink Overheat]
bit 6 ov [Overvoltage]
bit 7 Uv [Undervoltage]
bit 8 Reserved
bit 9 CE [Run at H5-34 (CE Go-To-Freq)]
bit A bUS [Option Communication Error]
bit B UL3/UL4 [Undertorque Detection 1/2]
bit C oH3 [Motor Overheat (PTC Input)]
bit D - E Reserved
bit F CALL [Serial Comm Transmission Error]
002B
Drive Input Terminal Status
bit 0 1: Drive Multi-Fuction Input Terminal S1 ON
bit 1 1: Drive Multi-Fuction Input Terminal S2 ON
bit 2 1: Drive Multi-Fuction Input Terminal S3 ON
bit 3 1: Drive Multi-Fuction Input Terminal S4 ON
bit 4 1: Drive Multi-Fuction Input Terminal S5 ON
bit 5 1: Drive Multi-Fuction Input Terminal S6 ON
bit 6 1: Drive Multi-Fuction Input Terminal S7 ON
bit 7 - F Reserved

Table of Contents