EasyManua.ls Logo

YASKAWA HV600

YASKAWA HV600
794 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Electrical Installation
3
3.3 Main Circuit Wiring
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference 83
Table 3.4 Output and Control Wiring
Model
H6BP
Motor Wiring
Standard Motor Terminal
Block TB1
Ground Wiring Control Wiring
AWG,
kcmil
Tightening
Torque
(in lb)
AWG, kcmil
Tightening
Torque
(in lb)
A1
Terminal Blocks
TB1, TB3-TB6
A1
Terminal Block
TB2 (FE)
A2
Terminal Blocks
TB1-TB4 and TB6
AWG, kcmil
Tightening
Torque
(in lb)
AWG, kcmil
Tightening
Torque
(in lb)
AWG, kcmil
Tightening
Torque
(in lb)
B001 14-2 32
14-10, 8, 6-4, or
2
35, 40, 45, or 50 24-16 4.4 to 5.3 24-18
*1
8.85 to 10.62 26-14 4
B002
14-2 32
14-10, 8, 6-4, or
2
35, 40, 45, or 50 24-16 4.4 to 5.3 24-18
*1
8.85 to 10.62 26-14 4
B003
14-2 32
14-10, 8, 6-4, or
2
35, 40, 45, or 50 24-16 4.4 to 5.3 24-18
*1
8.85 to 10.62 26-14 4
B004
14-2 32
14-10, 8, 6-4, or
2
35, 40, 45, or 50 24-16 4.4 to 5.3 24-18
*1
8.85 to 10.62 26-14 4
B007 14-2 32
14-10, 8, 6-4, or
2
35, 40, 45, or 50 24-16 4.4 to 5.3 24-18
*1
8.85 to 10.62 26-14 4
B011
14-2 32
14-10, 8, 6-4, or
2
35, 40, 45, or 50 24-16 4.4 to 5.3 24-18
*1
8.85 to 10.62 26-14 4
B014
14-2 32
14-10, 8, 6-4, or
2
35, 40, 45, or 50 24-16 4.4 to 5.3 24-18
*1
8.85 to 10.62 26-14 4
B021
14-2 32
14-10, 8, 6-4, or
2
35, 40, 45, or 50 24-16 4.4 to 5.3 24-18
*1
8.85 to 10.62 26-14 4
B027
14-2 32
14-10, 8, 6-4, or
2
35, 40, 45, or 50 24-16 4.4 to 5.3 24-18
*1
8.85 to 10.62 26-14 4
B034
14-2 32
14-10, 8, 6-4, or
2-1/0
35, 40, 45, or 50 24-16 4.4 to 5.3 24-18
*1
8.85 to 10.62 26-14 4
B040
14-2 32
14-10, 8, 6-4, or
2-1/0
35, 40, 45, or 50 24-16 4.4 to 5.3 24-18
*1
8.85 to 10.62 26-14 4
B052
14-2 32
14-10, 8, 6-4, or
2-1/0
35, 40, 45, or 50 24-16 4.4 to 5.3 24-18
*1
8.85 to 10.62 26-14 4
B065
14-2 32
14-10, 8, 6-4, or
2-1/0
35, 40, 45, or 50 24-16 4.4 to 5.3 24-18
*1
8.85 to 10.62 26-14 4
B077
6-2/0 120
14-10, 8, 6-4, or
2-1/0
35, 40, 45, or 50 24-16 4.4 to 5.3 24-18
*1
8.85 to 10.62 26-14 4
*1 24-16 is acceptable for solid wire or ferrule use only.
208 V Enclosed Wire Gauges and Torques
Table 3.5 Input Wiring
Model
H6BP
Standard Non-Fused
Input Disconnect Switch S1
With Option PM
Circuit Breaker CB1
Current Rating
Amps
AWG, kcmil
Tightening Torque
(in lb)
Current Rating
Amps
AWG, kcmil
Tightening Torque
(in lb)
D002 20 14-8 19 15 14-10 or 8-3/0 50 or 120
D003
20 14-8 19 15 14-10 or 8-3/0 50 or 120
D004
20 14-8 19 15 14-10 or 8-3/0 50 or 120
D007
20 14-8 19 20 14-10 or 8-3/0 50 or 120
D010 20 14-8 19 25 14-10 or 8-3/0 50 or 120
D016
20 14-8 19 40 14-10 or 8-3/0 50 or 120
D024
45 10, 8, or (6-2) 35, 40, or 50 60 14-10 or 8-3/0 50 or 120
D030
63 10, 8, or (6-2) 35, 40, or 50 70 14-10 or 8-3/0 50 or 120
D046
100 8-2/0 200 110 14-10 or 8-3/0 50 or 120
D059
100 8-2/0 200 125 14-10 or 8-3/0 50 or 120
D074
115 8-2/0 200 150 14-10 or 8-3/0 50 or 120

Table of Contents

Other manuals for YASKAWA HV600

Related product manuals