48
3.3 Wiring the iC9200
1. Strip the sheath covering the wires.
Expose the conductor by stripping the sheath about 8 to 9 mm from the tip.
2. Clamp the wire.
Push the conductor all the way into the plug and clamp it.
3.3.2 Wiring a Status Monitoring Device
Wire a status monitoring device to the RLY OUT connector on the iC9200. The RLY OUT connector is NO con-
tact relay output in a status output terminal. The terminal works in conjunction with the RDY LED indicator.
When the RDY LED indicator is lit, the terminal is short circuited, and when the RDY LED indicator is not lit,
the terminal is open.
The lit status of the RDY LED indicator means that the iC9200 is operating normally.
It does not mean that a user program is running.
(1) RLY OUT Connector Specifications
This connector works in conjunction with the RDY LED indicator on the iC9200.
RDY LED indicator is lit: Short circuited
RDY LED indicator is not lit: Open
(a) Contact Ratings
Input Voltage Current Capacity
24 VDC
0.5 A (resistive load)
0.25 A (inductive load)
(2) RLY OUT Connector Cable
For the RLY OUT connector cable, use a cable with a wire size of AWG28 to AWG14 (0.08 mm
2
to 2.0 mm
2
)
and a outer sheath diameter of 3.3 mm or less.
The procedure to create the RLY OUT connector cable is the same as that for the power cable.
(1) Creating the 24-VDC Power Cable on page 47