1.5 E: Motor Parameters
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual 125
Parameter Details
1
Figure 1.43
Figure 1.43 PM Motor Code
■ E5-02: Motor Rated Power (PM OLV)
Sets the rated power of the motor.
Note: This parameter is not reset when the drive is initialized using A1-03.
■ E5-03: Motor Rated Current (PM OLV)
Sets the motor rated current in amps.
Note: 1. The resolution of E5-03 depends on the rated output power of the drive. If a drive is set up for 7.5 kW
rated output power (ND or HD rating) the value will have two decimal places. It will have one decimal
place if a drive is set up for 11 kW and higher.
2. This parameter is not reset when the drive is initialized using A1-03.
■ E5-04: Number of Motor Poles (PM OLV)
Sets the number of motor poles.
Note: This parameter is not reset when the drive is initialized using A1-03.
No. Parameter Name Setting Range Default
E5-02 Motor Rated Power 0.10 to 18.50 kW
Depending on
E5-01
No. Parameter Name Setting Range Default
E5-03 Motor Rated Current
10 to 200% of drive
rated current
Depending on
E5-01
No. Parameter Name Setting Range Default
E5-04 Number of Motor Poles 2 to 48
Depending on
E5-01
0000
0: 1800 r/min Series
1: 3600 r/min Series
2: 1750 r/min Series
3: 1450 r/min Series
4: 1150 r/min Series
F: Special Motor
Motor Voltage Class
and Capacity
0: Pico Motor
(SMRA Series)
1: Derated Torque for IPM
Motors
(SSR 1 Series)