1.10 o: Operator Related Settings
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual 241
Parameter Details
1
Setting 0: No Action
The drive keeps a record of the fault trace and fault history.
Setting 1: Reset Fault Data
Resets the data for the U2- and U3- monitors. Once o4-11 is set to 1 and the
ENTER key is pressed, the fault data are erased and the display returns to 0.
o4-12: kWh Monitor Initialization
The kWh monitors U4-10 and U4-11 are not initialized when the power is cycled or the
drive is initialized. o4-12 can be used to manually reset them.
Setting 0: No Action
The kWh data are kept as they are.
Setting 1: Reset kWh Data
Resets the kWh counter. The monitors U4-10 and U4-11 will show 0. Once o4-12 is set to 1
and the ENTER key is pressed, the kWh data are erased and the display returns to 0.
o4-13: Number of Run Commands Counter Initialization
The Run command counter displayed in U4-02 is not reset when the power is cycled or the
drive is initialized. Using o4-13 it can be manually reset to 0.
Setting 0: No Action
The Run command data are kept as they are.
Setting 1: Reset kWh Data
Resets the Run command counter. The monitor U4-02 will show 0. Once o4-13 is set to 1
and the ENTER key is pressed, the counter value is erased and the display returns to 0.
q: FBD’s Parameters
q1-01 to q6-07: Reserved for Use by FBD’s
These parameters are reserved for use with FBD’s. Refer to the FBD’s manual for more
information.
No. Name Setting Range Default
o4-12 kWh Monitor Initialization 0 or 1 0
No. Name Setting Range Default
o4-13 Number of Run Commands Counter Reset 0 or 1 0