386 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
A.6 Parameters that Change with the Motor Code Selection
A.6 Parameters that Change with the Motor
Code Selection
The following tables show parameters and default settings that change with the motor code
selection E5-01 when Open Loop Vector for PM motors is used.
◆ Yaskawa Pico Motor (SPM motor)
Table A.8 1800 rpm Type Yaskawa Pico Motor Settings
Par. Description Unit Default Settings
E5-01
Motor Code − 0002 0003 0005 0006 0008
Voltage class − 200 Vac 200 Vac 200 Vac 200 Vac 200 Vac
Rated power − 0.4 kW 0.75 kW 1.5 kW 2.2 kW 3.7 kW
Rated speed r/min 1800 1800 1800 1800 1800
E5-02 Motor rated power kW 0.4 0.75 1.5 2.2 3.7
E5-03 Motor rated current A 2.1 4.0 6.9 10.8 17.4
E5-04 Motor pole number – 8 8 8 8 8
E5-05 Motor winding resistance W 2.47 1.02 0.679 0.291 0.169
E5-06 d-axis inductance mH 12.7 4.8 3.9 3.6 2.5
E5-07 q-axis inductance mH 12.7 4.8 3.9 3.6 2.5
E5-09 Induction voltage constant 1 mVs/rad 0 0 0 0 0
E5-24 Induction voltage constant 2 mV/(r/min) 62.0 64.1 73.4 69.6 72.2
E1-04 Maximum output frequency Hz 120 120 120 120 120
E1-05 Maximum output voltage V 200.0 200.0 200.0 200.0 200.0
E1-06 Base voltage Hz 120 120 120 120 120
E1-09 Minimum output frequency Hz 6 6 6 6 6
L3-24 Motor acceleration time s 0.064 0.066 0.049 0.051 0.044
n8-49 Pull-in current % 0 0 0 0 0