A.6 Parameters that Change with the Motor Code Selection
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual 387
Parameter List
A
Table A.9 3600 rpm Type Yaskawa Pico Motor Settings
Par. Description Unit Default Settings
E5-01
Motor Code − 0103 0105 0106 0108
Voltage class − 200 Vac 200 Vac 200 Vac 200 Vac
Rated power − 0.75 kW 1.5 kW 2.2 kW 3.7 kW
Rated speed r/min 3600 3600 3600 3600
E5-02 Motor rated power kW 0.75 1.5 2.2 3.7
E5-03 Motor rated current A 4.1 8.0 10.5 16.5
E5-04 Motor pole number – 8 8 8 8
E5-05 Motor winding resistance W 0.538 0.20 0.15 0.097
E5-06 d-axis inductance mH 3.2 1.3 1.1 1.1
E5-07 q-axis inductance mH 3.2 1.3 1.1 1.1
E5-09 Induction voltage constant 1 mVs/rad 0 0 0 0
E5-24 Induction voltage constant 2 mV/(r/min) 32.4 32.7 36.7 39.7
E1-04 Maximum output frequency Hz 240 240 240 240
E1-05 Maximum output voltage V 200.0 200.0 200.0 200.0
E1-06 Base voltage Hz 240 240 240 240
E1-09 Minimum output frequency Hz 12 12 12 12
L3-24 Motor acceleration time s 0.064 0.066 0.049 0.051
n8-49 Pull-in current % 0 0 0 0