1.4 d: Reference Settings
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual 97
Parameter Details
1
Figure 1.32
Figure 1.32 Preset Reference Timing Diagram
d2: Frequency Upper/Lower Limits
By entering upper or lower frequency limits, the drive programmer can prevent operation of
the drive above or below levels that may cause resonance and or equipment damage.
d2-01: Frequency Reference Upper Limit
Sets the maximum frequency reference as a percentage of the maximum output frequency.
This limit applies to all frequency references.
Even if the frequency reference is set to a higher value, the drive internal frequency
reference will not exceed this value.