1.8 L: Protection Functions
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual 209
Parameter Details
1
L4-07: Speed Agreement Detection Selection
Determines when frequency detection is active using parameters L4-01 through L4-04.
Setting 0: No Detection during Baseblock
Setting 1: Detection Always Enabled
L5: Fault Restart
The drive can be set up to performs a self-diagnostic check and resume the operation after a
fault has occurred. If the self-check is successful and the cause of the fault has disappeared,
the drive restarts by performing Speed Search (refer to b3: Speed Search on page 50 for
details).
The drive can attempt to restart itself following the faults listed below.
Use parameters L5-01 to L5-05 to set up automatic fault restart.
To output a signal during fault restart, set H2-01, H2-02, or H2-03 to 1E.
Do not use the fault restart function in hoist applications.
L5-01: Number of Auto Restart Attempts
Sets the number of number of times that the drive may attempt to restart itself.
No. Name Setting Range Default
L4-07 Speed Agreement Detection Selection 0 or 1 0
GF (Ground Fault) oL4 (Overtorque 2)
LF (Output Open Phase) ov (DC Bus Overvoltage)
oC (Overcurrent) PF (Input Phase Loss)
oH1 (Drive Overheat) rH (Braking Resistor Fault)
oL1 (Motor Overload) rr (Braking Transistor Fault)
oL2 (Drive Overload) Uv1
<1> When L2-01 is set to 1 or 2 (continue operation during momentary power loss)
(DC Bus Undervoltage)<1>
oL3 (Overtorque 1)