A.2 Parameter Table
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual 339
Parameter List
A
Note: Cycle power to the drive to enable MEMOBUS/Modbus settings.
L: Protection Function
L parameters provide protection to the drive and motor, such as: control during momentary
power loss, Stall Prevention, frequency detection, fault restarts, overtorque detection, torque
limits and other types of hardware protection.
H6-03
<22>
Pulse Train Input Gain
Sets the level of the value selected in H6-01
when a frequency with the value set in H6-02 is
input.
0.0 to
1000.0
100.0
%
AAA 42E 183
H6-04
<22>
Pulse Train Input Bias
Sets the level of the value selected in H6-01
when 0 Hz is input.
-100.0 to
+100.0
0.0% A A A 42F 183
H6-05
<22>
Pulse Train Input
Filter Time
Sets the pulse train input filter time constant.
0.00 to
2.00
0.10
s
AAA 430 183
H6-06
<22>
Pulse Train Monitor
Terminal MP
Selection
Select the pulse train monitor output function
(value of the - part of U-).
Refer to U: Monitors on page 364 for the list of
U monitors.
Example: To select U5-01, set “501.”
When not using this parameter or when using in
the through mode, set “000”.
000,
031,
101,
102,
105,
116,
501, 502
102 A A A 431 183
H6-07
<22>
Pulse Train Monitor
Scaling
Sets the terminal MP output signal frequency
when the monitor value is 100%. Set H6-06 to
“2” and H6-07 to “0”, to make the pulse train
monitor output equal to the output frequency.
0 to
32000
1440
Hz
AAA 432 184
<22> Parameter can be changed during run.
<39> If this parameter is set to 0, the drive will be unable to respond to MEMOBUS/Modbus commands.
<40> The availability of certain functions depends on the control method used.
No. Name Description Range Def.
Control
Mode
Addr.
Hex
Pg.
V/f
O
LV
P
M