A.2 Parameter Table
338 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
H5-04
Stopping Method
After Communication
Error
Selects the stopping method when a
communication time-out fault (CE) is detected.
0: Ramp to stop
1: Coast to stop
2: Fast-stop
3: Alarm only
0 to 3 3 A A A 428 263
H5-05
Communication Fault
Detection Selection
Enables or disables the communications time-
out fault (CE) detection.
0: Disabled
1: Enabled - If communication is lost for more
than two seconds, a CE fault will occur.
0,1 1 A A A 429 263
H5-06
Drive Transmit Wait
Time
Set the wait time between receiving and
sending data.
5 to 65 5 ms A A A 42A 263
H5-07 RTS Control Selection
Selects "request to send" (RTS) control:
0: Disabled - RTS is always on.
1: Enabled - RTS turns on only when sending.
0,1 1 AAA 42B 264
H5-09 CE Detection Time
Sets the time required to detect a
communications error. Adjustment may be
need when networking several drives.
0.0 to
10.0 s
2.0 s A A A 435 264
H5-10
Unit Selection for
MEMOBUS/Modbus
Register 0025H
Selects the units used for MEMOBUS/Modbus
register 0025H (Output Voltage Reference
Monitor).
0: 0.1 V units
1: 1 V units
0, 1 0 A A A 436 264
H5-11
Communications
ENTER Function
Selection
Select the function for the enter command that
saves parameter data to the drive.
0: Parameter changes are activated when
ENTER command is entered.
1: Parameter changes are activated immediately
without ENTER command (compatible with
Varispeed VS606-V7).
0, 1 1 A A A 43C 265
H5-12
Run Command
Method Selection
0: FWD/STOP, REV/STOP Method
1: RUN/STOP, FWD/REV Method
0, 1 0 A A A 43D 265
H6: Pulse Train Input/Output
Use H6 parameters to configure Pulse Train I/O operation.
H6-01
Pulse Train Input
Terminal RP Function
Selection
Selects pulse train input function.
0: Frequency reference
1: PID feedback value
2: PID setpoint value
3: V/f Control with Simple PG Feedback (can
be set only when using motor 1 in V/f Control)
0 to 3 0 A A A 42C 182
H6-02
<22>
Pulse Train Input
Scaling
Sets the terminal RP input signal frequency that
is equal to 100% of the value selected in H6-01.
1000 to
32000
1440
Hz
AAA 42D 183
No. Name Description Range Def.
Control
Mode
Addr.
Hex
Pg.
V/f
O
LV
P
M