2.9 MEMOBUS/Modbus Data Table
276 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
◆ Monitor Data
Monitor data can be read only.
0009H
Settings for Multi-Function Digital Outputs
bit 0 Contact Output (terminal MA/MB-MC)
bit 1 Photocoupler Output 1 (terminal P1-PC)
bit 2 Photocoupler Output 2 (terminal P2-PC)
bit 3 to bit 5 Reserved
bit 6 Enable Fault Contact Output (1 = enable bit 7)
bit 7 Fault Contact (terminal MA/MB-MC)
bit 8 to bit F Reserved
000AH Pulse Output Terminal MP Setting, 1 Hz units, Setting Range: 0 to 32000
000BH-000EH Reserved
000FH
Control Selection Setting
bit 0 Reserved
bit 1 PID Target Input
bit 2 to bit B Reserved
bit C Enable Terminal S5 Input for Broadcast Data
bit D Enable Terminal S6 Input for Broadcast Data
bit E Reserved
bit F Reserved
Register No. Contents
0020H
Drive Status 1
bit 0 During Run
bit 1 During Reverse
bit 2 Drive Ready
bit 3 Fault
bit 4 Data Setting Error
bit 5 Multi-Function Contact Output (terminal MA/MB-MC)
bit 6 Multi-Function Photocoupler Output 1 (terminal P1 - PC)
bit 7 Multi-Function Photocoupler Output 2 (terminal P2 - PC)
bit 8 to bit D Reserved
bit E ComRef status
bit F ComCtrl status
Register No. Contents