1.6 F: Option Settings
130 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
F6 and F7: Serial Communications Option Card Settings
These parameters are used for setting up communication option cards and communication
fault detection methods.
F6-01: Communications Error Option Selection
Determines the operation if a communication error occurs.
Setting 0: Ramp to Stop Using Current Accel/Decel Time
Setting 1: Coast to Stop
Setting 2: Fast Stop Using C1-09
Setting 3: Alarm Only, Continue Operation
F6-02: External Fault from Comm. Option Detection Selection
Determines the detection method of an external fault initiated by a communication option
(EF0).
Setting 0: Always Detected
Setting 1: Detection During Run Only
F6-03: External Fault from Comm. Option Operation Selection
Determines the operation when an external fault is initiated by a communication option
(EF0).
No. Parameter Name Setting Range Default
F6-01 Communications Error operation Selection 0 to 3 1
No. Parameter Name Setting Range Default
F6-02 External Fault from Comm. Option Selection 0 or 1 0
No. Parameter Name Setting Range Default
F6-03
External Fault from Comm. Option Operation
Selection
0 to 3 1