1.6 F: Option Settings
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual 131
Parameter Details
1
Setting 0: Ramp to Stop Using Current Accel/Decel Time
Setting 1: Coast to Stop
Setting 2: Fast Stop Using C1-09
Setting 3: Alarm only, Continue Operation
■
F6-04: Bus Error Detection Time
Sets the delay time for a “bUS” error detection.
■ F6-10: CC-Link Node Address
Sets the node address of a CC-Link option board if installed.
■ F6-11: CC-Link Communication Speed
Sets the communication speed for a CC-Link option card if installed.
Settings:
■
F6-14: BUS Error Auto Reset
Selects if a BUS error can be automatically reset if automatic fault retry is enabled.
No. Parameter Name Setting Range Default
F6-04 Bus Error Detection Time 0.0 to 5.0 s 2.0 s
No. Parameter Name Setting Range Default
F6-10 CC-Link Node Address 0 to 63 0
No. Parameter Name Setting Range Default
F6-11 CC-Link Communication Speed 0 to 4 0
F6-11 Communication Speed F6-11 Communication Speed
0 156 kbps 3 5 Mbps
1 625 kbps 4 10 Mbps
2 2.5 Mbps
No. Parameter Name Setting Range Default
F6-14 BUS Error Auto Reset 0 or 1 0