1.7 H: Terminal Functions
172 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
Setting 90 to 92: FBD’s Digital Output 1 to 3
These settings are for digital output functions used by FBD’s. Normally there is no need to
change or apply these settings.
Setting 100 to 192: Reverse Switching for Functions 0 to 92
These settings reverse the switching status of the specified function. Set as 1, where the
last to digits specify the setting number of the function to be reversed.
Examples:
• To reverse the output for “8: During Baseblock”, set “108”.
• To reverse the output for “4A: During KEB” set “14A”.
■ H2-06: Watt Hour Output Unit Selection
When one of the multi-function terminals is set to output the number of watt hours (H2-01/
02/03 = 39), parameter H2-06 determines the units for the output signal.
The output is intended to drive a watt hour meter or a PLC input by a 200 ms pulse signal. A
pulse is output according to the kWh unit selected in H2-06.
◆ H3: Multi-Function Analog Input Terminals
V1000 is equipped with 2 multi-function analog input terminals, A1 and A2. The user can
assign functions to these terminals by setting parameters H3-02 and H3-10 between 0 and
31.
■ H3-01: Terminal A1 Signal Level Selection
Selects the input signal level for analog input A1.
No. Parameter Name Setting Range Default
H2-06 Watt Hour Output Unit Selection
0: 0.1 kWh units
1: 1 kWh units
2: 10 kWh units
3: 100 kWh units
4: 1000 kWh units
0
No. Name Setting Range Default
H3-01 Terminal A1 Signal Level Selection 0 to 1 0