YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual 375
A.3 Control Mode Dependent Parameter Default Values
Parameter List
A
A.3 Control Mode Dependent Parameter
Default Values
The tables below list parameters that depend on the control mode selection (A1-02 for motor
1, E3-01 for motor 2). These parameters are initialized to the shown values if the control
mode is changed.
Table A.1 A1-02 (Motor 1 Control Mode) Dependent Parameters and Default Values
Para-
meter
<10> Default setting value is dependent on parameter E5-01, Motor Code Selection.
<12> Default setting value is dependent on parameter o2-04, Drive Model Selection.
<24> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
Description
Setting
Range
Resolutio
n
Control Modes (A1-02)
V/f (0) OLV (2) PM (5)
b3-02 Speed Search deactivation current 0 to 200 1% 120 100
b8-02 Energy Saving gain 0.0 to 10.0 0.1 0.7
C2-01 S-curve time at acceleration start 0.00 to 10.00 0.01 s 0.20 0.20 1.00
C3-01 Slip compensation gain 0.0 to 2.5 0.1 0.0 1.0
C3-02 Slip compensation time constant 0 to 10000 1 ms 2000 200
C4-01 Torque compensation gain 0.00 to 2.50 0.01 1.00 1.00 0.00
C4-02 Torque comp. primary delay time 0 to 10000 1 ms 200 20 100
C6-02 Carrier frequency 1 to F 1 <12> <12> 2
E1-04 Maximum output frequency 40.0 to 400.0 0.1 Hz 50.0 50.0 <10>
E1-05 Maximum output voltage <24> 0.0 to 255.0 0.1 V 200.0 200.0 <10>
E1-06 Base Frequency 0.0 to 400.0 0.1 Hz 50.0 50.0 <10>
E1-07 Middle output frequency 0.0 to 400.0 0.1 Hz 2.5 3.0
E1-08 Middle output freq. voltage <24> 0.0 to 255.0 0.1 V 16.0 14.4
E1-09 Minimum output frequency 0.0 to 400.0 0.1 Hz 1.3 0.5 <10>
E1-10 Minimum output voltage <24> 0.0 to 255.0 0.1 V 12.0 3.0
E1-11 Middle output frequency 2 0.0 to 400.0 0.1 Hz 0.0 0.0
E1-12 Middle output freq. voltage 2 <24> 0.0 to 255.0 0.1 V 0.0 0.0
E1-13 Base voltage <24> 0.0 to 255.0 0.1 V 0.0 0.0
L1-01 Motor protection selection 0 to 4 - 1 1 4
L3-20 Accel/Decel rate calculation rate 0.00 to 5.00 0.01 1.00 0.30 0.65
L3-21
Decel time at Stall Prevention
during acceleration
0.00 to 200.00 0.01 1.00 1.00 2.50