A.3 Control Mode Dependent Parameter Default Values
376 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
Table A.2 E3-01 (Motor 2 Control Mode) Dependent Parameters and Default Values
Para-
meter
<24> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
Description
Setting
Range
Resolutio
n
Control Modes (E3-
01)
V/f (0) OLV (2)
E3-04 Maximum output frequency 40.0 to 400.0 0.1 Hz 50.0 50.0
E3-05 Maximum output voltage <24> 0.0 to 255.0 0.1 V 200.0 200.0
E3-06 Base Frequency 0.0 to 400.0 0.1Hz 50.0 50.0
E3-07 Middle output frequency 0.0 to 400.0 0.1Hz 2.5 3.0
E3-08 Middle output freq. voltage <24> 0.0 to 255.0 0.1 V 16.0 14.4
E3-09 Minimum output frequency 0.0 to 400.0 0.1 Hz 1.3 0.5
E3-10 Minimum output voltage <24> 0.0 to 255.0 0.1 V 12.0 3.0
E3-11 Middle output frequency 2 0.0 to 400.0 0.1 Hz 0.0 0.0
E3-12 Middle output freq. voltage 2 <24> 0.0 to 255.0 0.1 V 0.0 0.0
E3-13 Base voltage <24> 0.0 to 255.0 0.1 V 0.0 0.0
E3-14 Motor 2 Slip compensation gain 0.0 to 2.5 0.1 0.0 1.0