1.7 H: Terminal Functions
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual 157
Parameter Details
1
If the digital input is open, the PID output builds the output frequency reference. If the input
is closed, the PID output is converted to bi-directional output frequency reference. Also refer
to d4-11: Bi-Directional Output Selection on page HIDDEN.
Setting 90 to 96: FBD’s Digital Input 1 to 7
These settings are for digital inputs functions used by FBD’s. Normally there is no need to
change or apply these settings.
Setting 9F: FBD’s Function Disable
This function is used to enable or disable a FBD’s program in the drive. An input
programmed for this function is effective only if A1-07 = 2.
H2: Multi-Function Outputs
H2-01 to H2-03: Terminal MA/MB/MC, P1/PC and P2/PC Function Selection
The drive has three multi-function output terminals. Set parameters H2-01 to H2-03 between
0 and 192 to assign functions to these terminals. Default values are listed in the table below.
Note: If not using an input terminal or if using it in the through-mode, be sure to set that terminal to
“F”.
Table 1.42 Multi-Function Output Terminal Settings
Status Description
Open FBD’s enabled
Closed FBD’s disabled
No. Parameter Name
Setting
Range
Default
H2-01 Terminal MA, MB and MC Function Selection (relay) 0 to 192 E: Fault
H2-02 Terminal P1 Function Selection (open-collector) 0 to 192 0: During Run
H2-03 Terminal P2 Function Selection (open-collector) 0 to 192 2: Speed Agree 1
Setting Function Page Setting Function Page
0 During Run
158
19 Torque Detection 2 (N.C.)
164
1 Zero Speed
159
1A During Reverse Operation
168
2 Speed Agree 1
159
1B During Baseblock (N.C.)
168
3 User Set Speed Agree 1
160
1C Motor 2 Selection
168