EasyManua.ls Logo

YASKAWA OYMC V1000

YASKAWA OYMC V1000
408 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
A.2 Parameter Table
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual 323
Parameter List
A
F: Options
F parameters are used to program the drive for PG feedback and to function with option
cards.
<38> If using a Yaskawa pico motor, the default setting is 1800 r/min.
<52> Parameter ignored when E3-11, Motor 2 Mid Output Frequency 2, and E3-12, Motor 2 Mid Output Frequency
Voltage 2, are set to 0.
<53> Default setting depends on the control mode for motor 2 set in parameter E3-01. The given value is for V/f
Control.
<57> Default setting value is dependent on parameter o2-04, Drive Model Selection and C6-01, Drive Duty Selection.
No. Name Description Range Def.
Control
Mode
Addr.
Hex
Pg.
V/f
O
LV
P
M
F1: V/f Control with Simple PG Feedback - PG Setup Parameters
Use F1 parameters to set up the drive for V/f Control with Simple PG Feedback. These parameters are enabled only
when H6-01 = 03
F1-02
Operation Selection at
PG Open Circuit
(PGO)
Sets stopping method when a PG open circuit
fault (PGO) occurs. Refer to parameter F1-14.
0: Ramp to Stop - Decelerate to stop using the
active deceleration time.
1: Coast to Stop
2: Fast-stop - Decelerate to stop using the
deceleration time in C1-09.
3: Alarm only - Drive continues operation.
0 to 3 1 A −− 381 128
F1-03
Operation Selection at
Overspeed (OS)
Sets the stopping method when an overspeed
(OS) fault occurs. Refer to F1-08 and F1-09.
0: Ramp to stop - Decelerate to stop using the
active deceleration time.
1: Coast to stop
2: Fast - Stop - Decelerate to stop using the
deceleration time in C1-09.
3: Alarm Only - Drive continues operation.
0 to 3 1 A −− 382 128
F1-04
Operation Selection at
Deviation
Sets the stopping method when a speed
deviation (DEV) fault occurs. Refer to F1-10
and F1-11.
0: Ramp to stop - Decelerate to stop using the
active deceleration time.
1: Coast to stop
2: Fast-stop - Decelerate to stop using the
deceleration time in C1-09.
3: Alarm only - Drive continues operation.
0 to 3 3 A −− 383 129