A.2 Parameter Table
322 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
E5-07
<25>
Motor q Axis
Inductance
Sets the q axis inductance in units of 0.01 mH.
0.00 to
600.00
<10> −−S32F126
E5-09
<25>
Motor
Induction
Voltage
Constant 1
Set the induced phase peak voltage in units of
0.1 mV (rad/s) [electrical angle].
Set this parameter when using a Yaskawa
SSR1 series PM motor with derate torque, or a
Yaskawa SST4 series motor with constant
torque.
When setting this parameter, E5-24 should be
set to 0. An alarm will be triggered if both E5-
09 and E5-24 are set to 0, or if neither
parameter is set to 0.
0.0 to
2000.0
<10> −−S 331 126
E5-24
<25>
Motor
Induction
Voltage
Constant 2
Set the induced phase-to-phase rms voltage in
units of 0.1 mV/(r/min) [mechanical angle].
Set this parameter when using a Yaskawa
SMRA series pico motor.
When setting this parameter, E5-09 should be
set to 0. An alarm will be triggered if both E5-
09 and E5-24 are set to 0, or if neither
parameter is set to 0.
If E5-03 (Motor Rated Current) is set to 0,
however, then an alarm will not be triggered
when both E5-09 and E5-24 are set to 0.
0.0 to
2000.0
0
<10>
−−S 353 127
<1> Default setting value is dependent on parameter A1-02, Control Method Selection. The value shown is for A1-02
= 2-OLV control.
<2> Default setting value is dependent on parameter A1-02, Control Method Selection. The value shown is for A1-02
= 0-V/f Control.
<4> Default setting value is dependent on parameter A1-06. This setting value is 0 when A1-06 = 0, and 1 when A1-06
does not = 0.
<10> Default setting value is dependent on parameter E5-01, Motor Code Selection.
<12> Default setting value is dependent on parameter o2-04, Drive Model Selection.
<17> Default setting value is dependent on parameter o2-04, Drive Capacity, when parameter H1- = 16 Motor 2 is
selected as a digital input. The value shown is when o2-04 = 98 (62H) 200 V class 0.4 kW drive.
<20> Range upper limit is dependent on parameters E5-01, Motor Code Selection, and A1-02, Control Method
Selection. The value shown is for A1-02 = 5-PM OLV control.
<21> Range upper limit is dependent on parameter E4-01 Motor 2 Rated Current.
<22> Parameter can be changed during run.
<24> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<25> Parameter setting value is not reset to the default value during drive initialization, A1-03 = 1110, 2220, 3330.
<26> Parameter ignored when E1-11, Motor 1 Mid Output Frequency 2, and E1-12, Motor 1 Mid Output Frequency
Voltage 2, are set to 0.0.
<27> Setting units for this parameter are determined by o2-04, Drive Model Selection. Less than 11 kW: 2 decimal
points, 11 kW and above: 1 decimal point.
<28> When parameter A1-02 = 5-PM OLV Control, E3-13 Motor 2 Base Voltage will be equal to T1-03, Motor Rated
Voltage, after Auto-Tuning the drive
<35> Default setting is determined by the V/f pattern selected to parameter E1-03.
<36> Default setting changes when using OLV Control for PM motors.
<37> Setting range becomes 0.00 to 130.00 for drives 0.2 kW and smaller.
No. Name Description Range Def.
Control
Mode
Addr.
Hex
Pg.
V/f
OL
V
PM

Table of Contents

Related product manuals