128 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
1.6 F: Option Settings
1.6 F: Option Settings
F1: Error Detection for V/f Control with PG
A one-track pulse signal can be connected to the V1000 pulse train input RP as speed
feedback. Using this signal for slip compensation improves the speed control accuracy. This
function is only available for motor 1.
The F1 parameters determine how the error detection for the speed feedback signal works.
Refer to C5: Automatic Speed Regulator (ASR) on page 86 for details how to activate ant
tune the function.
Operation at PG Fault Detection
The drive lets the user select from one of four possible operations when a fault occurs with
the PG encoder. The operation can be set up separately for each fault using parameters F1-
02/03/04. The table below list the stopping methods and the parameter setting values.
Table 1.39 Stopping Methods for PGo, oS, dEv Detection
NOTICE: Setting = 3: Alarm only. This setting offers limited protection to the motor and machinery. Take
proper precautions when selecting this setting.
F1-02: Operation Selection at PG Open Circuit (PGo)
Sets the stopping method when a PG open circuit fault (PGo) occurs. Refer to Table 1.39 for
setting explanations.
F1-03: Operation Selection at Overspeed
Sets the stopping method when an overspeed (oS) fault occurs. Refer to Table 1.39 for
setting explanations.
Description Setting
Ramp to Stop (uses the declaration time set to C1-02) 0
Coast to Stop 1
Fast Stop (uses the Fast Stop time set to C1-09) 2
Alarm only 3
No. Parameter Name Setting Range Default
F1-02 Operation Selection at PG Open Circuit (PGO) 0 to 3 1