A.2 Parameter Table
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual 337
Parameter List
A
No. Name Description Range Def.
Control
Mode
Addr.
Hex
Pg.
V/f
O
LV
P
M
H4: Multi-Function Analog Outputs
Use H4 parameters to configure the multi-function analog output terminals.
H4-01
Multi-Function
Analog Output
Terminal AM)
Selects the data to be output through multi-
function analog output terminal AM.
Set the desired monitor parameter to the digits
available in U-. For example, enter
“103” for U1-03.
When using this terminal in through mode or
when not using it at all, set “000” or “031”.
000 to
999
<40>
102 A A A 41D 180
H4-02
<22>
Multi-Function
Analog Output
Terminal AM Gain
Sets terminal AM output level when selected
monitor is at 100%.
Maximum output voltage is 10 V.
-999.9 to
999.9
100.0
%
SSS 41E181
H4-03
<22>
Multi-Function
Analog Output
Terminal AM Gain
Sets terminal AM output level when selected
monitor is at 0%.
-999.9 to
999.9
0.0% A A A 41F 181
H5: MEMOBUS/Modbus Communications
Use H5 Parameters to connect the drive to a MEMOBUS/Modbus network.
H5-01
<39>
Drive Node Address
Selects drive station node number (address) for
MEMOBUS/Modbus terminals R+, R-, S+, S-.
Cycle power for the setting to take effect.
0 to
20 H
1F A A A 425 262
H5-02
Communication Speed
Selection
Selects the baud rate for MEMOBUS/Modbus
terminals R+, R-, S+ and S-. Cycle power for
the setting to take effect.
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps
5: 38400 bps
6: 57600 bps
7: 76800 bps
8: 115200 bps
0 to 8 3 A A A 426 262
H5-03
Communication Parity
Selection
Selects the communication parity for
MEMOBUS/Modbus terminals R+, R-, S+ and
S-. Cycle power for the setting to take effect.
0: No parity
1: Even parity
2: Odd parity
0 to 2 0 A A A 427 262