1.7 H: Terminal Functions
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual 183
Parameter Details
1
■ H6-02: Pulse Train Input Terminal RP Scaling
The pulse train input scaling parameter sets the terminal RP input frequency that is equal to
100% of the signal selected as the input value in parameter H6-01.
■ H6-03: Pulse Train Input Terminal RP Gain
Sets the level of the value selected in H6-01 when a pulse train signal with the frequency set
in H6-02 is input to terminal RP.
■ H6-04: Pulse Train Input Terminal RP Bias
Sets the level of the value selected in H6-01 when a 0 Hz signal is input to terminal RP.
■ H6-05: Pulse Train Input Terminal RP Filter Time
Sets the pulse train input filter time constant in seconds.
■ H6-06: Pulse Train Output Terminal MP Monitor Selection
Selects the pulse train monitor output terminal MP function. The set value is equal to
the numerals in U- of the selected monitor. Refer to U: Monitors on page 364 for a
complete list of monitors. Selectable monitor items are listed below.
No. Name Setting Range Default
H6-02 Pulse Train Input Scaling 1000 to 32000 Hz 1440 Hz
No. Name Setting Range Default
H6-03 Pulse Train Input Gain 0.0 to 1000.0% 100.0%
No. Name Setting Range Default
H6-04 Pulse Train Input Bias -100.0 to 100.0% 0.0%
No. Name Setting Range Default
H6-05 Pulse Train Input Filter Time 0.00 to 2.00 s 0.10 s
No. Name Setting Range Default
H6-06
Pulse Train Output Terminal MP Monitor
Selection
000, 031, 101, 102,
105, 116, 501, 502,
801 to 809
102