EasyManua.ls Logo

YASKAWA OYMC V1000

YASKAWA OYMC V1000
408 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
A.5 Defaults Determined by Drive Capacity (o2-04) and Normal/Heavy
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual 385
Parameter List
A
No. Description Unit Setting Range
Model VZA 47P5 4011 4015
C6-01 Normal/Heavy Duty Sel. HD ND HD ND HD ND
o2-04 Drive Model Selection 9A 9C 9D
E2-11
(E4-11,
T1-02)
Motor rated power kW 7.5 11.0 11.0 15.0 15.0 18.5
b3-06 Speed Search current 1 0.5 0.5 0.5 0.5 0.5 0.5
b8-04 Energy saving coefficient 145.38 140.88 140.88 126.26 126.26 115.74
C6-02 Carrier frequency 373737
E2-01
(E4-01,
T1-04)
Motor rated current A 13.3 19.9 19.9 26.5 26.5 32.9
E2-02
(E4-02)
Motor rated slip Hz 1.30 1.70 1.70 1.60 1.60 1.67
E2-03
(E4-03)
Motor no-load current A 4.0 5.6 5.6 7.6 7.6 7.8
E2-05
(E4-05)
Motor line-to-line
resistance
1.152 0.922 0.922 0.550 0.550 0.403
E2-06
(E4-06)
Motor leakage inductance % 15.5 19.6 19.6 17.2 17.2 20.1
E2-10
(E4-10)
Motor Iron Loss W 263 385 385 440 440 508
E5-01 Motor Code hex FFFF FFFF FFFF FFFF FFFF FFFF
L2-02
Momentary power loss
ride-through time
s112222
L2-03
Momentary power loss
Baseblock time
s 0.8 0.9 0.9 1.0 1.0 1.0
L2-04
Momentary power loss
voltage recovery time
s 0.3 0.3 0.3 0.6 0.6 0.6
L2-05 UV detection voltage V dc 380 380 380 380 380 380
L3-24 Motor acceleration time s 0.175 0.265 0.265 0.244 0.244 0.317
L8-02 Overheat alarm level °C 110 110 110 110 110 110
L8-09 Ground fault selection 111111
L8-35 Installation Method Sel. 222222
L8-38
Carrier frequency
reduction selection
222222
n1-03
Hunting Prevention Time
Constant
ms 10 10 10 10 10 10

Table of Contents

Related product manuals