1.7 H: Terminal Functions
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual 155
Parameter Details
1
4
Multi-Step
Speed
Reference
> 0 --
0
When the Up 2 is enabled, drive
accelerates up to the frequency
reference plus d4-03 (bias is
increased for d4-03).
When Down 2 is enabled, drive
decelerates down to the frequency
reference minus d4-03 (bias is
decreased for d4-03).
Holds output frequency (holds the
bias) when no Up 2 or Down 2 input
or both active.
Resets the bias when the reference
changes
Operates with the frequency
reference in all other situations.
Not saved
51
If the bias and frequency
reference are constant for 5 s,
the bias is added to the active
frequency reference and reset
afterwards.
6
Other
(analog
communic
ations, etc.)
00
0
Accelerates (increases the bias) while
the Up 2 function is closed
Decelerates (decreases the bias)
while Down 2 is closed
Holds output frequency (holds the
bias) when no Up 2 or Down 2 input
or both active.
When during accel/decel. the
frequency reference changes for
more then d4-07, bias value is held
until the output frequency meets the
reference (speed agree).
Not saved
71
If the bias is constant for 5 s, is
is saved to parameter d4-06.
The frequency reference cannot
be overwritten, so only the bias
is saved.
8
Other:
Analog,
Comm.,
etc.)
01--
Accelerates (increases the bias) while
the Up 2 function is closed,
Decelerates (decreases the bias)
while Down 2 is closed.
Otherwise operates at the frequency
reference
Not saved
9
>0 --
0
When the Up 2 is enabled, drive
accelerates up to the frequency
reference plus d4-03 (increases the
bias for d4-03).
When Down 2 is enabled, drive
decelerates down to the frequency
reference minus d4-03 (decreases the
bias for d4-03).
When during accel/decel the
frequency reference changes for
more then d4-07, bias value is held
until the output frequency meets the
reference (speed agree).
Not saved
10 1
If the bias is constant for 5 s, is
is saved to parameter d4-06.
The frequency reference cannot
be overwritten, so only the bias
is saved.
Con-
dition
Freq. Ref.
Source
d4-03 d4-05 d4-01 Operation Frequency Saved