1.1 A: Initialization
26 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
Setting 1: Water Supply Pump Application
Table 1.5 Water Supply Pump Parameters Settings
Table 1.6 Water Supply Pump: Preferred Parameters (A2-01 to A2-16)
Setting 2: Conveyor Application
Table 1.7 Conveyor: Parameter Settings
No. Name Optimum Setting
A1-02 Control Method Selection 0: V/f Control
b1-04 Reverse Operation Selection 1: Reverse Prohibited
C1-01 Acceleration Time 1 1.0 s
C1-02 Deceleration Time 1 1.0 s
C6-01 Duty Rating 1: Normal Duty
E1-03 V/f Pattern Selection 0FH
E1-07 Mid Output Frequency 30.0
E1-08 Mid Output Frequency Voltage 50.0
L2-01
Momentary Power Loss Operation
Selection
1: Enabled
L3-04
Stall Prevention Selection during
Deceleration
1: Enabled
No. Parameter Name No. Parameter Name
b1-01 Frequency Reference Selection E1-07 Mid Output Frequency
b1-02 Run Command Selection E1-08 Mid Output Frequency Voltage
b1-04 Reverse Operation Selection E2-01 Motor Rated Current
C1-01 Acceleration Time 1 H1-05
Multi-Function Digital Input Terminal
S5 Function Selection
C1-02 Deceleration Time 1 H1-06
Multi-Function Digital Input Terminal
S6 Function Selection
E1-03 V/f Pattern Selection L5-01 Number of Auto Restart Attempts
No. Parameter Name Optimum Setting
A1-02 Control Method Selection 0: V/f Control
C1-01 Acceleration Time 1 3.0 s
C1-02 Deceleration Time 1 3.0 s
C6-01 Duty Rating 0: Heavy Duty