EasyManua.ls Logo

YASKAWA OYMC V1000

YASKAWA OYMC V1000
408 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2.9 MEMOBUS/Modbus Data Table
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual 281
MEMOBUS/Modbus
Communications
2
00B0H Option Code
Register contains ASCII code of 3rd and 4th digit of the option card type
number. Example: Register value is 5343H for “P3” if a SI-P3 option card
is installed.
00B5H
Frequency Reference
After Soft-starter
r/min units
<4>
00B6H 0.01% units
00B7H
Frequency Reference
r/min <4>
00B8H 0.01% units
00BFH oPE Error Number
00C0H
Fault contents 3
bit 0 Reserved
bit 1 Undervoltage (Uv1)
bit 2 Control Power Supply Undervoltage (Uv2)
bit 3 Soft Charge Circuit Fault (Uv3)
bit 4 Reserved
bit 5 Ground Fault (GF)
bit 6 Overcurrent (oC)
bit 7 Overvoltage (ov)
bit 8 Heatsink Overheat (oH)
bit 9 Heatsink Overheat (oH1)
bit A Motor Overload (oL1)
bit B Drive Overload (oL2)
bit C Overtorque Detection 1 (oL3)
bit D Overtorque Detection 2 (oL4)
bit E Dynamic Braking Transistor Fault (rr)
bit F Braking Resistor Overheat (rH)
00C1H
Fault contents 4
bit 0 External Fault at input terminal S3 (EF3)
bit 1 External Fault at input terminal S4 (EF4)
bit 2 External Fault at input terminal S5 (EF5)
bit 3 External Fault at input terminal S6 (EF6)
bit 4 Reserved
bit 5 Overspeed (oS)
bit 6 Excessive Speed Deviation (dEv)
bit 7 PG Disconnected (PGo)
bit 8 Input Phase Loss (PF)
bit 9 Output Phase Loss (LF)
bit A Motor Overheat (PTC input) (oH3)
bit B Digital Operator Connection Fault (oPr)
bit C EEPROM Write Error (Err)
bit D Motor Overheat Fault (PTC input) (oH4)
Register No. Contents