2.9 MEMOBUS/Modbus Data Table
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual 283
MEMOBUS/Modbus
Communications
2
00C8H
Alarm contents 2
bit 0 Undervoltage (Uv)
bit 1 Overvoltage (ov)
bit 2 Heatsink Overheat (oH)
bit 3 Drive Overheat (oH2)
bit 4 Overtorque 1 (oL3)
bit 5 Overtorque 2 (oL4)
bit 6 Run Commands Input Error (EF)
bit 7 Drive Baseblock (bb)
bit 8 External Fault 3, input terminal S3 (EF3)
bit 9 External Fault 4, input terminal S4 (EF4)
bit A External Fault 5, input terminal S5 (EF5)
bit B External Fault 6, input terminal S6 (EF6)
bit C Reserved
bit D Reserved
bit E Cooling Fan Error (FAN)
bit F Overspeed (oS)
00C9H
Alarm contents 3
bit 0 Excessive Speed Deviation (dEv)
bit 1 PG Disconnected (PGo)
bit 2 Digital Operator Connection Fault (oPr)
bit 3 MEMOBUS/Modbus Communication Error (CE)
bit 4 Option Communication Error (bUS)
bit 5 Serial Communication Transmission Error (CALL)
bit 6 Motor Overload (oL1)
bit 7 Drive Overload (oL2)
bit 8 Reserved
bit 9 Option Card External fault (EF0)
bit A Motor 2 Switch command input during run (rUn)
bit B Reserved
bit C Serial Communication Transmission Error (CALL)
bit D Undertorque Detection 1 (UL3)
bit E Undertorque Detection 2 (UL4)
bit F MEMOBUS/Modbus Test Mode Fault (SE)
Register No. Contents