A.2 Parameter Table
302 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
b3-18
Speed Search Restart
Detection Time
Sets the time in seconds for Speed Search
restart to be detected.
0.00 to
1.00
0.10
s
AA 1F1 58
b3-19
Number of Speed
Search Restarts
Sets the number of restarts possible for Speed
Search restart operations.
0 to 10 3 A A 1F2 58
b3-24
Speed Search Method
Selection
Sets the Speed Search detection mode.
0: Current Detection Type
1: Speed Estimation Type
0,1 0 A A 1C0 58
b3-25
Speed Search Retry
Interval Time
Sets the wait time before Speed Search restarts. 0 to 30.0 0.5 s A A A 1C8 58
b4: Timer Function
Use b4 parameters to configure timer function operation.
b4-01
Timer Function
On-Delay Time
Used in conjunction with a multi-function
digital input (H1- = 18) and a multi-
function digital output (H2- = 12)
programmed for the timer function. This sets
the amount of time between digital input
closure and digital output activation.
0.0 to
300.0
0.0 s A A A 1A3 59
b4-02
Timer Function
Off-Delay Time
Used in conjunction with a multi-function
digital input (H1- = 18) and a multi-
function digital output programmed for the
timer function. This sets the amount of time the
output remains activated after the digital input
is opened.
0.0 to
300.0
0.0 s A A A 1A4 59
b5: PID Control
Use b5 parameters to configure the PID control drive function.
b5-01 PID Function Setting
Sets the PID control mode.
0: Disabled
1: Enable (PID output = freq. ref., PID input is
D-controlled)
2: (PID output = freq. ref., PID feedback is D-
controlled)
3: Enable (PID output added to freq. ref., PID
input is D-controlled)
4: Enable (PID output added to freq. ref., PID
feedback is D-controlled)
0 to 4 0 A A A 1A5 64
b5-02
<22>
Proportional Gain
Setting (P)
Sets the proportional gain of the PID controller.
A setting of 0.00 disables P control.
0.00 to
25.00
1.00 A A A 1A6 64
b5-03
<22>
Integral Time Setting
(I)
Sets the integral time for the PID controller. A
setting of 0.0 s disables integral control.
0.0 to
360.0
1.0 s A A A 1A7 64
b5-04
<22>
Integral Limit Setting
Sets the maximum output possible from the
integrator.
0.0 to
100.0
100.0
%
AAA 1A8 65
No. Name Description Range Def.
Control
Mode
Addr.
Hex
Pg.
V/f
O
LV
P
M