A.2 Parameter Table
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual 305
Parameter List
A
b6: Dwell Function
Use b6 parameters to configure dwell function operation.
b6-01
Dwell Reference at
Start
The Dwell function is used to temporarily hold
the frequency when driving a motor with a
heavy load.
Parameters b6-01 and b6-02 set the frequency
to hold and the time to maintain that frequency
at start.
Parameters b6-03 and b6-04 set the frequency
to hold and the time to maintain that frequency
at stop.
0.0 to
400.0
0.0
Hz
AAA 1B6 73
b6-02 Dwell Time at Start
0.0 to
10.0
0.0 s A A A 1B7 73
b6-03
Dwell Frequency at
Stop
0.0 to
400.0
0.0
Hz
AAA 1B8 73
b6-04 Dwell Time at Stop
0.0 to
10.0
0.0 s A A A 1B9 73
b8: Energy Saving
Use b8 parameters to configure the energy saving/conservation drive function.
b8-01
Energy Saving Control
Selection
Selects the Energy Savings function.
0: Disabled
1: Enabled
0,1 0 A A 1CC 74
b8-02
<22>
Energy Saving Gain
Sets energy savings control gain when in Open
Loop Vector Control.
0.0 to
10.0
0.7 A 1CD 74
b8-03
<22>
Energy Saving Control
Filter Time Constant
Sets energy saving control filter time constant
when in Open Loop Vector Control.
0.00 to
10.00
0.50 A 1CE 74
b8-04
Energy Saving
Coefficient Value
Sets the Energy Saving coefficient and is used
to fine adjustments in V/f Control.
0.0 to
655.00
<57>
A −− 1CF 74
b8-05
Power Detection Filter
Time
Sets a filter time for the Power Detection used
by Energy Savings in V/f Control.
0 to
2000
20
ms
A −− 1D0 75
b8-06
Search Operation
Voltage Limit
Sets the limit for the voltage search operation
performed by Energy Savings in V/f Control.
Set as a percentage of the motor base voltage.
Disabled when set to 0%.
0 to 100 0% A −− 1D1 75
<1> Default setting value is dependent on parameter A1-02, Control Method Selection. The value shown is for A1-02
= 2-OLV control.
<2> Default setting value is dependent on parameter A1-02, Control Method Selection. The value shown is for A1-02
= 0-V/f Control.
<5> Default setting is dependent on parameter b5-20, PID Setpoint Scaling.
<12> Default setting value is dependent on parameter o2-04, Drive Model Selection.
<14> Default setting value is dependent on parameter o2-09, Initialization Spec. Selection.
No. Name Description Range Def.
Control
Mode
Addr.
Hex
Pg.
V/f
O
LV
P
M
10
Time
Run command
Output
Frequency