A.2 Parameter Table
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual 315
Parameter List
A
d7: Offset Frequency
Use d7 parameters to set the offset frequency.
d7-01
<22>
Offset Frequency 1
Added to the frequency reference when the
digital input “Frequency Offset 1” (H1- =
44) is switched on.
-100.0 to
+100.0
0.0% A A A 2B2 108
d7-02
<22>
Offset Frequency 2
Added to the frequency reference when the
digital input “Frequency Offset 2” (H1- =
45) is switched on.
-100.0 to
+100.0
0.0% A A A 2B3 108
d7-03
<22>
Offset Frequency 3
Added to the frequency reference when the
digital input “Frequency Offset 3” (H1- =
46) is switched on.
-100.0 to
+100.0
0.0% A A A 2B4 108
<11> Default setting value is dependent on parameter o1-03, Digital Operator Display Selection.
<19> Range upper limit is dependent on parameters E1-04, Maximum Output Frequency, and d2-01, Frequency
Reference Upper Limit.
<22> Parameter can be changed during run.
No. Name Description Range Def.
Control
Mode
Addr.
Hex
Pg.
V/f
O
LV
P
M