A.2 Parameter Table
342 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
L2-11
<24>
Desired DC Bus
Voltage during KEB
Sets the desired value of the DC bus voltage
during KEB.
150 to
400 V
E1-
01 x
1.22
AAA 461 197
L3: Stall Prevention Function
Use L3 parameters to configure the Stall Prevention function.
L3-01
Stall Prevention
Selection during
Acceleration
Selects the Stall Prevention method used to
prevent excessive current during acceleration.
0: Disabled - Motor accelerates at active
acceleration rate. The motor may stall if load is
too heavy or accel time is too short.
1: General Purpose - When output current
exceeds L3-02 level, acceleration stops.
Acceleration will continue when the output
current level falls below the L3-02 level.
2: Intelligent - The active acceleration rate is
ignored. Acceleration is completed in the
shortest amount of time without exceeding the
current value set in L3-02.
0 to 2
<29>
1 A A A 48F 197
L3-02
Stall Prevention Level
during Acceleration
Used when L3-01 = 1 or 2.
100% is equal to the drive rated current.
Decrease the set value if stalling or excessive
current occurs with default setting.
0 to 150
<7> AAA 490 199
L3-03
Stall Prevention Limit
during Acceleration
Sets Stall Prevention lower limit during
acceleration when operating in the constant
power range. Set as a percentage of the drive's
rated current.
0 to 100 50% A A A 491 199