A.2 Parameter Table
346 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
L5-02
Auto Restart
Operation Selection
Sets fault contact (H2- = E) activation
during automatic restart attempts.
0: Fault output not active.
1: Fault output active during restart attempt.
0,1 0 A A A 49F 210
L5-04
Fault Reset Interval
Time
Sets the amount of time to wait between
performing fault restarts. Enabled when L5-05
is set to 1.
0.5 to
600.0 s
10.0 s A A A 46C 210
L5-05
Fault Reset Operation
Selection
Selects the method of incrementing the restart
counter.
0: Continuously attempt to restart and
increment counter after successful restart (same
as Varispeed VS616-F7/G7)
1: Attempt to restart with the interval time set in
L5-04. Every trial increments the counter.
(same as Varispeed VS606-V7)
0 to 1 0 A A A 467 210