A.2 Parameter Table
352 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
L8-15
OL2 Characteristics
Selection at Low
Speeds
Sets the OL2 characteristics at output
frequencies below 6 Hz.
0: No OL2 level reduction below 6Hz.
1: OL2 level is reduced linearly below 6 Hz. It
is halved at 0 Hz.
0,1 1 A A A 4BB 221
L8-18 Soft CLA Selection
Selects the software current limit function.
Typically no adjustment is required.
0: Disabled
1: Enabled
0,1 1 A A 4BE 222
L8-19
Frequency Reduction
Rate during OH
Pre-Alarm
Specifies the frequency reference reduction
gain at overheat prealarm when L8-03 = 4.
0.1 to
1.0
0.8 A A A 4BF 219
L8-29
Current Unbalance
Detection (LF2)
Selects the detection of unbalanced output
currents caused by faulty devices in the output
circuit.
0: Disabled
1: Enabled
0 to 1 1 −−A4DF222
L8-35
Installation Method
Selection
Selects the installation type:
0: Standard installation of Open Chassis drive
1: Side-by-Side installation with top cover
removed
2: Standard Installation of NEMA Type 1 drive
3: Finless / Fin outside installation
0 to 3
<12>
<25>
ΑΑA4ECH222
L8-38
Carrier Frequency
Reduction
Provides protection to the IGBTs by reducing
the carrier frequency at low speeds.
0: Disabled
1: Enabled below 6Hz
2: Enabled for the whole speed range
0 to 2
<12> AAA 4EF 223
L8-40
Carrier Frequency
Reduction Time
Sets the time for that the drive continues
running with reduced carrier frequency after the
carrier reduction condition has gone (see also
L8-38).
A setting of 0.00 s disables the carrier
frequency reduction time.
0.00 to
2.00
0.50 A A A 4F1 224
L8-41
High Current Alarm
Selection
Configures an alarm when the output current
exceeds 150% of the drive rated current.
0: Alarm disabled.
1: Alarm enabled.
0,1 0 A A A 4F2 224
<2> Default setting value is dependent on parameter A1-02, Control Method Selection. The value shown is for A1-02
= 0-V/f Control.
<7> Default setting value is 120% when C6-01 is set to 1 (ND) and 150% when C6-01 is set to 0 (HD).
<9> Default setting value is dependent on parameter E1-01, Input Voltage Setting.
<10> Default setting value is dependent on parameter E5-01, Motor Code Selection.
<12> Default setting value is dependent on parameter o2-04, Drive Model Selection.
No. Name Description Range Def.
Control
Mode
Addr.
Hex
Pg.
V/f
O
LV
P
M