A.2 Parameter Table
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual 359
Parameter List
A
o4-02
Accumulated
Operation Time
Selection
Determines, how the cumulative operation time
(U4-01) is counted.
0: Logs power-on time
1: Logs operation time when the drive output is
active (output operation time).
0 to 1 0 A A A 50C 239
o4-03
Cooling Fan Operation
Time Setting
Sets the value of the fan operation time monitor
U1-03 in units of 10 h.
<61>
0 to
9999
0AAA50E239
o4-05
Capacitor
Maintenance Setting
Sets the value of the capacitor maintenance
time monitor U4-05.
0 to 150 0% A A A 51D 240
o4-07
Soft Charge Bypass
Relay Maintenance
Setting
Sets the value of the Soft Charge Bypass Relay
Maintenance monitor U4-06.
0 to 150 0% A A A 523 240
o4-09
IGBT Maintenance
Setting
Sets the value of the IGBT Maintenance
monitor U4-07.
0 to 150 0% A A A 525 240
o4-11
U2, U3 Initialize
Selection
Selects if U2- (Fault Trace), U3- (Fault
History) monitors are reset at drive
initialization.
0: Saves the fault monitor data
1: Resets the fault monitor data
0 to 1 0 A A A 510 240
o4-12
kWh Monitor
Initialize Selection
Selects if U4-10 and U4-11 (kWh monitor) are
reset at drive initialization.
0: Saves the U4-10 and U4-11 monitor data.
1: Resets the U4-10 and U4-11 monitor data.
0 to 1 0 A A A 512 241
o4-13
Number of Run
Commands Initialize
Selection
Selects if the Run command counter (U4-02) is
reset at drive initialization.
0: Saves the number of Run commands
1: Resets the number of Run commands
0 to 1 0 A A A 528 241
<9> Default setting value is dependent on parameter E1-01, Input Voltage Setting.
<11> Default setting value is dependent on parameter o1-03, Digital Operator Display Selection.
<12> Default setting value is dependent on parameter o2-04, Drive Model Selection.
<22> Parameter can be changed during run.
<61> Valid for drive software 1011 and later. Value is set in 1 h units for older software.
No. Name Description Range Def.
Control
Mode
Addr.
Hex
Pg.
V/f
O
LV
P
M