A.2 Parameter Table
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual 367
Parameter List
A
U1-24 Input Pulse Monitor Displays the Pulse Train input RP frequency. 32000 7D
U1-25 Software No. (Flash) Flash ID
No signal
output
available
4D
U1-26 Software No. (ROM) ROM ID
No signal
output
available
5B
U2: Fault Trace
Use U2 monitor parameters to view fault trace data.
U2-01 Current Fault Display of the current fault.
No signal
output avail.
–AAA80
U2-02 Previous Fault Display of the previous fault.
No signal
output avail.
–AAA81
U2-03
Frequency Reference
at Previous Fault
Displays the frequency reference at the
previous fault.
No signal
output avail.
0.01
Hz
AAA 82
U2-04
Output Frequency at
Previous Fault
Displays the output frequency at the previous
fault.
No signal
output avail.
0.01
Hz
AAA 83
U2-05
Output Current at
Previous Fault
Displays the output current at the previous
fault.
No signal
output avail.
AAA 84
U2-06
Motor Speed at
Previous Fault
Displays the motor speed at the previous fault.
No signal
output avail.
0.01
Hz
A 85
U2-07
Output Voltage at
Previous Fault
Displays the output voltage at the previous
fault.
No signal
output avail.
0.1 V A A A 86
U2-08
DC Bus Voltage at
Previous Fault
Displays the DC bus voltage at the previous
fault.
No signal
output avail.
1 V A A A 87
U2-09
Output Power at
Previous Fault
Displays the output power at the previous
fault.
No signal
output avail.
0.1
kW
AAA 88
U2-10
Torque Reference at
Previous Fault
Displays the torque reference at the previous
fault.
No signal
output avail.
0.1% −Α− 89
U2-11
Input Terminal Status
at Previous Fault
Displays the input terminal status at the
previous fault. Displayed as in U1-10.
No signal
output avail.
–AAA8A
U2-12
Output Terminal
Status at Previous
Fault
Displays the output status at the previous
fault. Displays the same status displayed in
U1-11.
No signal
output
available
–AAA8B
U2-13
Drive Operation Status
at Previous Fault
Displays the operation status of the drive at
the previous fault. Displays the same status
displayed in U1-12.
No signal
output
available
–AAA8C
U2-14
Cumulative Operation
Time at Previous Fault
Displays the cumulative operation time at the
previous fault.
No signal
output
available
1 H A A A 8D
No. Name Description
Analog
Output Level
Unit
Control
Mode
Addr.
Hex
V/f
O
LV
P
M