A.5 Defaults Determined by Drive Capacity (o2-04) and Normal/Heavy
382 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
No. Description Unit Default Settings
Model VZA 27P5 2011 2015
C6-01 Normal/Heavy Duty HD ND HD ND HD ND
o2-04 Drive Model Selection Hex 6B 6D 6E
E2-11
(E4-11,
T1-02)
Motor rated power kW 7.5 11.0 11.0 15.0 15.0 18.5
b3-06 Speed Search current 1 0.5 0.5 0.5 0.5 0.5 0.5
b8-04 Energy saving coefficient 72.69 70.44 70.44 63.13 63.13 57.87
C6-02 Carrier frequency 373737
E2-01
(E4-01,
T1-04)
Motor rated current A 26.6 39.7 39.7 53 53 65.8
E2-02
(E4-02)
Motor rated slip Hz 1.3 1.7 1.7 1.6 1.6 1.67
E2-03
(E4-03)
Motor no-load current A 8.0 11.2 11.2 15.2 15.2 15.7
E2-05
(E4-05)
Motor line-to-line
resistance
0.288 0.230 0.230 0.138 0.138 0.101
E2-06
(E4-06)
Motor leakage inductance % 15.5 19.5 19.5 17.2 17.2 15.7
E2-10
(E4-10)
Motor Iron Loss W 262 245 245 272 272 505
E5-01 Motor Code hex FFFF FFFF FFFF FFFF FFFF FFFF
L2-02
Momentary power loss
ride-through time
s 1.0 1.0 2.0 2.0 2.0 2.0
L2-03
Momentary power loss
Baseblock time
s 0.8 0.9 0.9 1.0 1.0 1.0
L2-04
Momentary power loss
voltage recovery time
s 0.3 0.3 0.3 0.3 0.6 0.6
L2-05 UV detection voltage V dc 190 190 190 190 190 190
L3-24 Motor acceleration time s 0.175 0.265 0.265 0.244 0.244 0.317
L8-02 Overheat alarm level °C 121 121 120 120 120 120
L8-09 Ground fault selection 111111
L8-35 Installation Method Sel. 222222
L8-38
Carrier frequency
reduction selection
222222
n1-03
Hunting Prevention Time
Constant
ms 10 10 10 10 10 10