1.2 b: Application
42 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
Figure 1.7
Figure 1.7 DC Injection Braking to Stop
The time for DC Injection Braking is determined by the value set to b2-04 and by the output
frequency at the time the Run command is removed. It can be calculated by:
Figure 1.8
Figure 1.8 DC Injection Braking Time Depending on Output Frequency
Note: If an overcurrent (oC) fault occurs during DC Injection Braking to stop, lengthen the minimum
baseblock time (L2-03) until the fault no longer occurs.
Run
command
Output
frequency
ON OFF
DC Injection Braking
Time at Stop (b
2-04)*
Minimum Baseblock Time (
L2-03)
DC Injection Current (
b2-02)
DC Injection
braking
Motor speed
DC Injection brake time
b2-04 10 Output frequency
Max. output frequency (E1-04)
=
Output frequency when
Stop command was entered
100%
(Maximum output
frequency)
10%
DC Injection braking time
b2-0410
b2-04