1.2 b: Application
54 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
Figure 1.16
Figure 1.16 Current Detection Speed Search at Start or external Speed Search
Note: When the Run command is set the drive waits at least for the Speed Search Wait Time (b3-05)
before Speed Search is performed, even if the Minimum Baseblock Time is set to smaller values
than b3-05.
Notes on Using Current Detection Type Speed Search
Increase the voltage recovery ramp time set to L2-04 if a UV1 fault occurs when
performing Current Detection Speed Search.
Shorten the Speed Search deceleration time set to b3-03 if an OL1 fault occurs while
performing Current Detection Speed Search.
Current Detection Speed Search is not available when using Open Loop Vector Control
for PM motors.
Increase the minimum baseblock time set to L2-03 if an overcurrent fault occurs when
performing Speed Search after power is restored following a momentary power loss.
Activation of Speed Search
Speed Search can be activated as described below. Independent of the activation method the
Speed Search type must be selected in parameter b3-24.
1. Automatically at every Run command (refer to b3-01: Speed Search Selection at Start on
page 55). With this setting external Speed Search commands are disregarded.
2. By digital inputs:
The following input functions for H1- can be used.
Run command
Output
frequency
Output current
OFF ON
b3-02
Decel time set
set to b3-03
Waits for twice
as long as L2-04
Selected
frequency
reference
Minimum Baseblock Time (L2-03)
Max. output frequency
or the specified
frequency reference