1.2 b: Application
70 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
Figure 1.22
Figure 1.22 PID Sleep Operation
Notes on using the PID Sleep function:
The PID Sleep function is always active, even if PID control is disabled.
The method the Sleep function uses to stop the motor is defined by parameter b1-03.
The parameters necessary to set up the PID Sleep function are explained below.
b5-15: PID Sleep Level
Sets the level used for PID Sleep.
The drive goes into Sleep mode if the PID output or frequency reference is smaller than b5-
15 for longer than the time set in b5-16. It resumes the operation when the PID output or
frequency reference is above b5-15 for longer than the time set in b5-16.
b5-16: PID Sleep Delay Time
Sets the delay time to activate or deactivate the PID Sleep function.
b5-17: PID Accel/Decel Time
The PID acceleration/deceleration time is applied on the PID setpoint value.
As the normal acceleration times C1- are applied after the PID output, they reduce the
responsiveness of the system and can cause hunting or over- and undershooting when the
No. Name Setting Range Default
b5-15 PID Sleep Level 0.0 to 400.0 Hz 0.0 Hz
No. Name Setting Range Default
b5-16 PID Sleep Delay Time 0.0 to 25.5 s 0.0 s
PID Output
PID Sleep Level ( b5-15)
Sleep Delay Time
Sleep Delay Time
Run command enabled
Continues to output “During Run”
Internal Run
command
External Run
command
During Run
Stop
b5-16 b5-16
Run