<4. Setting converter>
4-19
IM 12A01G01-03EN 1st Edition : Mar. 25, 2021-00
Figure 4.13 Address CH assignment and mA output
n MODBUS - Converter
FLXA402T as slave communicates with HOST devices, via MODBUS RS-485, or Ethernet
(Modbus TCP/IP). Select a network system according to the hardware architecture you use.
For further technical information on MODBUS, read TI 12A01F01-62EN.
4.6.2 Ethernet setting (E)
Modbus TCP/IP is available by Ethernet cable-connection between the converter and master
devices.
Interface Ethernet
Maximum session times 2
Protocol Modbus//TCP
Port number 502
Ethernet 10/100 Mbps speed rate, Internet Protocol version 4 (IPv4)
Set “DHCP enable” to “On” if you want DHCP server to assign IP address automatically. Set it
“O” (O is default) if you use a static IP address.
When you use a static IP address, set “Subnet mask” and “Default gateway”, according to
Ethernet you use.
The next table shows default of Ethernet parameter.
Parameter name Default
DHCP O
IP address 192.168.1.10
Subnet mask 255.255.255.0
Default gateway 192.168.1.1
NOTE
After rebooting FLXA402T (Power OFF/ON), Ethernet setting is valid.