<4. Setting converter>
4-15
IM 12A01G01-03EN 1st Edition : Mar. 25, 2021-00
4.5 Display settings
Congure display related settings.
4.5.1 Display 1, 2, 3, 4 settings
Home screen has two switchable pages, each page displays up to 4 items to monitor.
display
1
display
2
display
3
display
1
display
2
display
4
Figure 4.12 Home screen sample (4 process display (left), 2 process display (right))
Assign Display 1, 2, 3, 4 to each item to display.
l Process parameter slot
FLXA402T allows multiple sensor connection, according to specication you choose.
Determine sensors to display from “Sensor 1-1”, “Sensor 1-2”, “Converter”. Don’t use “Sensor
2-2”.
If you want to display a converter parameter (mA input), on the line 1/2, select “Converter.”
You can assign one sensor connection number to multiple Displays.
For instance, if you place Sensor 1-1 on Display 1 and Display 2, you can monitor two di󰀨erent
item of Sensor 1-1 on a single page, e.g. both process value and temperature of Sensor 1-1.
You need to assign MODBUS address to the sensors in advance. Read 4.6.1 MODBUS
setting
l 1st/2nd line
On Main screen you can set parameters to display as 1st/2nd line items.
Parameters you can select to display are as follows:
TB: Turbidity
FC: Residual Chlorine Concentration, Temperature
PH: pH, Temperature
SC: Conductivity , Temperature
Converter: AI
Inappropriate parameter settings cause conguration fail. When display setting fails, not only the
fail location but all of the 1st/2nd lines on Main screen show “----” as measured value.
When selecting “Converter” among Process parameter slot, set only converter parameters to
display, such as mA input value.
NOTE
You cannot enter “Empty” at 1st line of Display1-1.
l Display name
You can assign 12 characters or less to the display name. Display name is displayed on Home/
Main/Monitor screens.