Heating-side control output
Current/voltage pulse output
Cooling-side control
output
Cooling-side control
output
12
13
11
12
13
12
13
A
b
B
23
24
25
26
27
SDB(+)
SDA(-)
RDB(+)
RDA(-)
SG
8
9
10
L
N
1
2
3
NC
NO
COM
48
49
50
NC
NO
COM
+
-
+
-
CAUTION
Before carrying out wiring, turn off the power
to the controller and check that cables to be
connected are not alive with a tester or the like
because there is a possibility of electric shock.
Power supply
Power supply
Relay contact output
Contact rating: 250 V AC, 3 A
30 V DC, 3 A (resistance load)
Contact rating: 250 V AC, 3 A
30 V DC, 3 A (resistance load)
*Time proportional PID relay contact
output is configured at factory
before shipment.
*Time proportional PID
relay contact output is
configured at factory
before shipment.
* Wiring can only be carried out for controllers
with communication functions.
Maximum baud rate: 9600 bps
*
Wiring can only be carried out for
controllers with remote input.
TC input
RTD input
mV/V input
21
22
Remote input
Specify in a range of
1-5 V DC, 0-2 V DC,
or 0-10 V DC.
-
+
RS-485 communication
Relay contact output
Default: 1-5 V DC
OT1=4 (factory-set default) OT1=5
Correspondence between parameter OT1 and heating side output types/cooling side output types
OT1=6
OT1=7 OT1=8 OT1=9 OT1=10 OT1=11 OT1=12
The types of control output,
“relay output” and “voltage pulse output
” shown in the table above refer to those of time proportional control.
To change to a relay output for on-off control, select
“Relay Terminals
” and change the setpoint of the proportional band to
“0.”
Heating side: Relay output
(terminals , and )
Cooling side: Relay output
(terminals , and )
1
2
3
Heating side: Voltage pulse output
(terminals and )
Cooling side: Relay output
(terminals , and )
16
17
Heating side: Current output
(terminals and )
Cooling side: Relay output
(terminals , and )
16
17
Heating side: Relay output
(terminals , and )
Cooling side: Voltage pulse output
(terminals and )
1
2
3
Heating side: Relay output
(terminals , and )
Cooling side: Current output
(terminals and )
1
2
3
Heating side: Voltage pulse output
(terminals and )
Cooling side: Voltage pulse output
(terminals and )
16
17
Heating side: Current output
(terminals and )
Cooling side: Voltage pulse output
(terminals and )
16
17
Heating side: Voltage pulse output
(terminals and )
Cooling side: Current output
(terminals and )
16
17
Heating side: Current output
(terminals and )
Cooling side: Current output
(terminals and )
16
17
* Factory-set to “PV retransmission.
”
* Retransmission output 1 is not available if a
15 V DC loop power supply is used.
Heating-side
control output
14
15
Retransmission output 1
*
4-20 or
0-20 mA DC
14
15
15 V DC loop power supply
*
14.5-18.0 V DC
(21 mA DC max.)
* Retransmission output 2 is available
only when “relay” is selected as the
type of heating-side control output.
Default: 4-20 mA DC
-
+
-
+
*
The functionality of a contact input can be varied by changing the setting of the contact
input registration parameter.
* OT1 is a setup parameter.
You can change the settings of the parameter OT1 to
change the control output type.
See "2. Initial Settings".
19
18
External contact inputs
40
39
38
37
20
28
30
DI1
DI2
DI3
DI4
DI5
DI6
COM
COM
DI8
AUTO when DI1=ON
MAN when DI1=OFF
STOP when DI2=ON
RUN when DI2=OFF
DI3
DI4
1.SP2.SP3.SP4.SP
ON
ONOFF
OFF
ON
ON OFF
OFF
5.SP6.SP7.SP8.SP
ON
ONOFF
OFF
ON
ON OFF
OFF
DI5
DI6
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
ON
Common
Remote when DI8=ON
Local when DI8=OFF
Common
When switching among target setpoints 1 to 8:
19
18
40
39
38
37
20
28
30
DI1
DI2
DI3
DI4
DI5
DI6
COM
COM
DI8
+5V
+5V
+5V
+5V
+5V
+5V
36
DI7
36
DI7
+5V
+5V
Contact Transistor contact
Contact rating: 12 V DC, 10 mA or more
No function
UT
* If all of the contact inputs are set to OFF,
the controller uses the immediately
preceding target setpoint.
6
5
External contact outputs
4
7
34
33
DO1
DO2
DO3
COM
DO4
DO5
No function
Alarm 1 output
Alarm 2 output
Alarm 3 output
Common
Alarm 4 output
32
DO6
31
DO7
35
COM
No function
Common
UT
FAIL output
(ON when normal)
Relay contact rating: 240 V AC, 1 A
30 V DC, 1 A (resistance load)
Transistor contact rating: 24 V DC, 50 mA
48
47
46
47
46
47
46
47
46
47
46
47
46
49
50
48
49
50
48
49
50
46
47
+
-
0-20 mA DC
4-20 mA DC,
voltage pulse (12 V)
PV input
16
17
Current/voltage
pulse output
0-20mADC,
4-20mADC
Voltage pulse (12 V)
16
17
Retransmission
output 2*
Default: 4-20 mA DC
0-20mADC,
4-20mADC
-
+
-
+
A
llowable range: 100-240 V AC (
10%)
(free voltage)
50/60 Hz shared
Load resistance: 600
Ω or less
12
13
Note: Connecting a 250
Ω resistor to the terminals is
optional.
Model: X010-250-2 (resistor with M3.5 crimp-on terminal
lugs)
*
When receiving 4-20 mA DC current signals,
set the PV input type to 1-5 V DC (setpoint
“41”).
䊏
Receiving 4-20 mA DC Current
Signals with the Controller
250 Ω
4-20mA
-
+
* Not configured at factory before shipment
See "2. Initial Settings".
Default: Unspecified
retransmission type
Note: Select this option from
the OT1 parameter.
Note: Select this option from the
OT1 parameter.
Note: Select this option from the OT1 parameter.
Note: External Contact Input
If the power is turned on when the external contact input is OFF,
the mode (SPN, R/L, or A/M) existing before the power is turned
off will be continued. (except for RUN/STOP)
Relay Transistor
* When “relay contact output
” is selected as the type of cooling-side
control output,
“current output terminal
” can be used for retransmission output 2.
16
17
Retransmission output value is same as and terminals.
* When “current / voltage pulse
” is selected
as the type of heating-side control output,
these can be used for alarm 4 output.